XT5042-CU - Multifunction Digital Timer
XT5042-CU
XT5042-CU - Multifunction Digital Timer
Panel Mount
Features
• Multifunction - 7 Timing Functions
• 9 Time Ranges, Seconds/Minutes/Hours
• Dual Display, 4 Digit, 7 segment LED
• 2 Setpoints

DATA Sheet Link
< Product photo may vary depending on part number selection.
Analog / Digital Protection Relays
Protection
Altech is pleased to offer a variety of protection relays covering:
Phase Monitoring
Voltage Monitoring
Current Monitoring
Frequency Monitoring
Current Leakage / Ground Fault Monitoring Protection relays help to maintain systems and ensure that proper action is taken when a fault is detected. Such functions help to preserve productivity and operational effectiveness of integral components.
- Process Controllers - Supply Voltage
- 85-270V AC/DC
- Process Controllers - LED Indication
- LED 1: Relay 1, LED 2: Relay 2, LED 3: sec., LED 4: Min., LED 5: Hrs.
- Process Contollers - Input Voltage
- 85-270V AC/DC (50/60Hz)
- Process Controllers - Main Output
- 2 SPST - 2NO - 5 @ 230V AC
- Process Controllers - Reset
- Front, Remote/ Power interruption (programmable)
- Process Controllers - Power Consumption
- 5VA max
- Process Controllers - Operating Temperature
- 0 to 50°C (32 to 122°F)
- Process Controllers - Storage Temperature
- -20 to 75°C (-4 to 167°F)
- Process Controllers - Humidity (Non-Condensing)
- 95% Relative Humidity
- Process Controllers - Weight
- 175 grams (.385 lbs)
- Process Controllers - Display Type
- Liquid Crystal Display with backlight
- Process Controllers - Digits
- 2 rows of 4 digits
- Process Controllers - Protection Level
- IP65 (for faceplate)
- Process Controllers - Set Points
- 2
- Process Controllers - Modes
- ON delay / Interval / Cyclic ON first / Cyclic OFF first / Forward-pause-reverse / Instantaneous+delayed batch
- Process Controllers - Counting Direction
- Up/Down
- Process Controllers - Memory
- 10 years
- Process Controllers - Time Ranges
- 0-99.99 sec 0-999.9 sec/min/hr 0-9999 sec/min/hr 0-99:59 min: sec 0-99:59 hr:min
- Process Controllers - Start Input
- Gate / Pulse start (programmable)
- Process Controllers - Timer
- Setting +/-5% of Full Scale Repeat +/-0.5% or 50m sec.